Parameter Groups
‑223‑
Min.:
0
Unit:
kWh
Max.: 65535 Data type: UInt16
Default:
0
Change: Unchangeable
Value Range:
0 kWh to 65535 kWh
Description
This parameter shows the accumulative power consumption of the AC drive.
F7-15
Temporary performance software version
Address:
0xF70F
Min.:
0
Unit:
Max.: 0 Data type: UInt16
Default:
0
Change: Unchangeable
Value Range:
0.00 to 0.00
Description
Indicates the temporary performance software version of the AC drive.
F7-16
Temporary function software version
Address:
0xF710
Min.:
0
Unit:
Max.: 0 Data type: UInt16
Default:
0
Change: Unchangeable
Value Range:
0.00 to 0.00
Description
Indicates the temporary function software version of the AC drive.
2.9 F8 Auxilliary Function
F8-00
Jog frequency
Address:
0xF800
Min.:
0
Unit:
Hz
Max.: F0‑10 Data type: UInt16
Default:
2
Change: In real time
Value Range:
0.00 Hz to value of F0‑10
Description
This parameter defines the running frequency of the AC drive in the jogging mode.