Function Application
618
Figure 3‑69 Forward/reverse run switchover dead zone time
Related parameter
Para. No. Function Default
Value Range Description
F8‑12
Forward/Reverse run
switchover dead zone time
0.0s 0.0s to 3000.0s
Used to set the transition period
when the output is 0 Hz during
forward/reverse run switchover of
the AC drive.
3.5.5 Timing Function
The timer starts from 0 upon startup of the AC drive. When the timing duration (F8‑44)
expires, the AC drive automatically stops, and the DO outputs the active signal. You
can use U0‑20 to view the remaining running time.
The DO outputs the active signal when the accumulative power‑on time (F7‑13) of
the AC drive exceeds the accumulative power‑on time threshold (F8‑16).
The DO outputs the active signal when the accumulative running time (F7‑09) of
the AC drive exceeds the accumulative running time threshold (F8‑17).