Function Application
‑619‑
Parameters
Para.
Function
Default Value Range
Description
F8‑42
Timing
function
0
0: Disabled
1: Enabled
When F8‑42 (timing function) is set to
1 and the running time of the AC drive
reaches the specified timing duration,
the DO outputs the active signal. The
timing duration is set through F8‑43
and F8‑44.
F8‑43
Scheduled
running time
selection
0 0: F8‑44
1: AI1
2: AI2
If this parameter is set to 0, the timing
duration is determined by F8‑44.
If this parameter is set to 1, the timing
duration can be calculated through
the following formula: Timing
duration = (AI1 voltage/10 V) x F8‑44.
100% of the analog input range
corresponds to the value of F8‑44.
If this parameter is set to 2, the timing
duration can be calculated through
the following formula: Timing
duration = (AI2 voltage/10 V) x F8‑44.
100% of the analog input range
corresponds to the value of F8‑44.
F8‑44
Scheduled
running time
0.0 min 0.0 min to
6500.0 min
The timing duration is set through F8‑
43 and F8‑44.
Table 3–34 Power‑on time threshold
Para.
Function
Default Value Range
Description
F8‑16
Accumulative
power‑on
time
threshold
0 h 0 h to 65000 h This parameter is used to set the
accumulative power‑on time
threshold of the AC drive. When F7‑13
(accumulative power‑on time) exceeds
F8‑16 (accumulative power‑on time
threshold), the DO outputs the active
signal.
Table 3–35 Running time reach
Para.
Function
Default Value Range
Description
F8‑17
Accumula
tive running
time
threshold
0 h 0 h to 65000 h This parameter is used to set the
accumulative running time threshold
of the AC drive. When F7‑09
(accumulative running time) exceeds
F8‑17 (accumulative running time
threshold), the DO outputs the active
signal.