Function Application
‑541‑
Use this auto‑tuning method when the motor is not allowed to rotate during auto‑
tuning.
Table 3–12 Procedure of static auto‑tuning on all parameters of synchronous motor
Step Description
1
Power on the AC drive, and then set F0‑02 to 0 to select the operating panel as command source.
2
Enter motor parameters (F1‑00 to F1‑05) according to its nameplate.
3
Set F1‑37 to 13 (static auto‑tuning on all parameters of synchronous motor) and press "ENTER" on the
operating panel. The display on the panel is:
4
Press and hold the RUN key for longer than 3s. The motor auto‑tuning starts. The RUN indicator is steady
on, the TUNE/TC indicator blinks, and the AC drive energizes the motor.
When the preceding display disappears and the operating panel returns to normal parameter display
state, auto‑tuning is completed.
Parameters F1‑06, F1‑17, and F1‑18 are obtained.
Manually set F1‑19 (SVC and PMVVC), F1‑31 (FVC), and F1‑30 (FVC).