Function Application
‑493‑
3 Function Application
3.1 Drive Configuration
3.1.1 Command Sources
3.1.1.1 Setting Command Sources
Commands are used to control operations of the AC drive, such as start, stop, forward
run, reverse run, and jogging. Command sources include the operating panel,
terminals, and communication. You can select the command source through F0‑02.
Para.
No.
Function Default
Value Range Description
F0‑02
Command
source
selection
0
0: Operating panel
1: Terminal
2: Communication
Defines the source of control commands, including start/
stop, forward run, reverse run, and jog.
0: Operating panel
Control commands are input using the RUN, STOP/RES,
and MF.K keys on the operating panel. This mode is
suitable for initial commissioning.
1: Terminal
Control commands are input through DI terminals of the
AC drive. This mode is suitable for most applications.
2: Communication
Control commands are input through remote
communication. The AC drive must be equipped with a
communication card to communicate with the host
controller. This mode is suitable for remote control and
centralized control on multiple devices or systems.
3.1.1.2 Setting Commands Through the Operating Panel
Set F0‑02 to 0 and use the
and
keys on the operating panel to
control the AC drive.
Press
to start the AC drive (the RUN indicator is on).
When the AC drive is running, press
to stop the AC drive (the RUN
indicator is off).