Function Application
‑611‑
Figure 3‑62 Reverse frequency inhibition
Related parameters
Para.
No.
Function Default
Value Range Description
F8‑13 Reverse run enable 0
0: Reverse running allowed
1: Reverse running inhibited
When F8‑13 is set to 0, enter a reverse
command to the AC drive and the motor will
run at zero frequency.
F0‑09
Running direction
selection
0
0: Default direction
1: Opposite to the default
direction
You can change the rotation direction of the
motor by editing this parameter without
changing the motor wiring. Editing this
parameter is equivalent to changing any two of
the motors U, V, W wires.
3.5.2.5 Detection Width for Frequency Reach
You can use F8‑21 to set the detection width for frequency reach. The following figure
shows the timing diagram of this function.