Parameter Groups
‑240‑
Description
This parameter defines the deceleration time for emergency stop.
F8-57
Accumulative power consumption cleared
Address:
0xF839
Min.:
0
Unit:
‑
Max.: 1 Data type: UInt16
Default:
0
Change:
At stop
Value Range:
0: Disabled
1: Enabled
Description
When this parameter is set to 1, the accumulative output power consumption of
the AC drive will be cleared.
F8-58
Output power correction coefficient
Address:
‑
Min.:
0
Unit:
%
Max.: 200 Data type: UInt16
Default:
100
Change:
At stop
Value Range:
0.0% to +200.0%
Description
When the output power (U0‑05) is not equal to expected value, perform linear
correction on the output power via this parameter.
2.10 F9 Fault and Protection
F9-00
AC drive overload suppression
Address:
0xF900
Min.:
0
Unit:
‑
Max.: 1 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0: Disabled
1: Enabled
Description