Parameter Groups
‑239‑
Max.: F8‑49 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0.00 Hz to value of F8‑49
Description
During AC drive running, when the frequency reference is lower than or equal to
F8‑51 (Hibernating frequency), the AC drive enters the hibernating state and
coasts to stop after the time set by F8‑52 (Hibernating delay) expires.
F8-52
Hibernation delay time
Address:
0xF834
Min.:
0
Unit:
s
Max.: 6500 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0.0s to 6500.0s
Description
During AC drive running, when the frequency reference is lower than or equal to
F8‑51 (Hibernating frequency), the AC drive enters the hibernating state and
coasts to stop after the time set by F8‑52 (Hibernating delay) expires.
F8-53
Current running time reached
Address:
0xF835
Min.:
0
Unit: min
Max.: 6500 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0.0 min to 6500.0 min
Description
When the current running time reaches the value of F8‑53, the DO outputs an
active signal. It is valid only for the current AC drive running. The previous running
time is not added.
F8-55
Deceleration time for emergency stop
Address:
0xF837
Min.:
0
Unit:
s
Max.: 6500 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0.0s to 6500.0s