Parameter Groups
‑238‑
F8-48
Cooling Fan control
Address:
0xF830
Min.:
0
Unit:
‑
Max.: 1 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0: Working during drive running
1: Working continuously
Description
When this parameter is set to 0, the fan works when the AC drive is running. When
the AC drive stops, the fan works if the heatsink temperature is higher than 40°C
and stops if the heatsink temperature is lower than 40°C.
When this parameter is set to 1, the fan keeps working after power‑on.
F8-49
Wakeup frequency
Address:
0xF831
Min.:
F8‑51
Unit:
Hz
Max.: F0‑10 Data type: UInt16
Default:
0
Change: In real time
Value Range:
F8‑51 to F0‑10
Description
In hibernating state, when the frequency reference is equal to or larger than F8‑49
(Wakeup frequency) and the current running command is valid, the AC drive
wakes up after the time set by F8‑50 (Wakeup delay) expires.
F8-50
Wakeup delay
Address:
0xF832
Min.:
0
Unit:
s
Max.: 6500 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0.0s to 6500.0s
Description
In hibernating state, when the frequency reference is equal to or larger than F8‑49
(Wakeup frequency) and the current running command is valid, the AC drive
wakes up after the time set by F8‑50 (Wakeup delay) expires.
F8-51
Hibernation frequency
Address:
0xF833
Min.:
0
Unit:
Hz