EasyManua.ls Logo

Inovance MD500-PLUS Series - Page 238

Inovance MD500-PLUS Series
718 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Groups
‑237‑
Description
The scheduled running time is set by F8‑43 and F8‑44.
F8-45
AI1 input voltage lower limit
Address:
0xF82D
Min.:
0
Unit:
V
Max.: F8‑46 Data type: UInt16
Default:
3.1
Change: In real time
Value Range:
0.00 V to F8‑46
Description
When the AI1 input is higher than F8‑46 (AI1 input voltage upper limit) or lower
than F8‑45 (AI1 input voltage lower limit), the DO outputs an "AI1 input limit
exceeded" active signal to indicate whether the AI1 input voltage is in the setting
range.
F8-46
AI1 input voltage upper limit
Address:
0xF82E
Min.:
F8‑45
Unit:
V
Max.: 11 Data type: UInt16
Default:
6.8
Change: In real time
Value Range:
F8‑45 to 11.00 V
Description
When the AI1 input is higher than F8‑46 (AI1 input voltage upper limit) or lower
than F8‑45 (AI1 input voltage lower limit), the DO outputs an "AI1 input limit
exceeded" active signal to indicate whether the AI1 input voltage is in the set
range.
F8-47
Module temperature reached
Address:
0xF82F
Min.:
0
Unit: °C
Max.: 100 Data type: UInt16
Default:
75
Change: In real time
Value Range:
0°C to 100℃
Description
When the heatsink temperature reaches the value of F8‑47, the DO outputs an
active signal.