Parameter Groups
‑236‑
Description
Detection width of current 2 = F8‑41 (detection width of current 2) x F1‑03 (Rated
motor current)
F8-42
Timing function
Address:
0xF82A
Min.:
0
Unit:
‑
Max.: 1 Data type: UInt16
Default:
0
Change:
At stop
Value Range:
0: Disabled
1: Enabled
Description
When F8‑42 is set to 1 and the current running of the AC drive reaches the
specified timing duration, the DO outputs an active signal. The timing duration is
set by F8‑43 and F8‑44.
F8-43
Scheduled running time selection
Address:
0xF82B
Min.:
0
Unit:
‑
Max.: 3 Data type: UInt16
Default:
0
Change:
At stop
Value Range:
0: Set by F8‑44 (Timing duration)
1: AI1
2: AI2
3: AI3
Description
When this parameter is set to 0, the scheduled running time is set by F8‑44.
When this parameter is set to 1, the scheduled running time equals to the result of
(AI1 voltage/10 V) x F8‑44. 100% of analog input corresponds to the value of F8‑44.
When this parameter is set to 2, the scheduled running time equals to the result of
(AI2 voltage/10 V) x F8‑44 100% of analog input corresponds to the value of F8‑44.
F8-44
Scheduled running time
Address:
0xF82C
Min.:
0
Unit: min
Max.: 6500 Data type: UInt16
Default:
0
Change:
At stop
Value Range:
0.0 min to 6500.0 min