Parameter Groups
‑235‑
F8-38
Detection level of current 1
Address:
0xF826
Min.:
0
Unit:
%
Max.: 300 Data type: UInt16
Default:
100
Change: In real time
Value Range:
0.0% to 300.0%
Description
When the output current of the AC drive is in the range of F8‑38 (Detection level of
current 1) ± F8‑39 (Detection width of current 1) x F1‑03 (Rated motor current),
the DO outputs an active signal.
F8-39
Detection width of current 1
Address:
0xF827
Min.:
0
Unit:
%
Max.: 300 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0.0% to 300.0%
Description
Detection width of current 1 = F8‑39 (detection width of current 1) x F1‑03 (Rated
motor current)
F8-40
Detection level of current 2
Address:
0xF828
Min.:
0
Unit:
%
Max.: 300 Data type: UInt16
Default:
100
Change: In real time
Value Range:
0.0% to 300.0%
Description
When the output current of the AC drive is in the range of F8‑40 (Detection level of
current 2) ± F8‑41 (Detection width of current 2) x F1‑03 (Rated motor current),
the DO outputs an active signal.
F8-41
Detection width of current 2
Address:
0xF829
Min.:
0
Unit:
%
Max.: 300 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0.0% to 300.0%