EasyManua.ls Logo

Inovance MD500-PLUS Series - Page 235

Inovance MD500-PLUS Series
718 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Groups
234
0.0% to 300.0%
Description
When the output current of the AC drive is lower than or equal to F8‑34 (Zero
current detection level) for a period exceeding F8‑35 (Zero current detection
delay), the DO outputs an active signal.
F8-35
Zero current detection delay
Address:
0xF823
Min.:
0.01
Unit:
s
Max.: 600 Data type: UInt16
Default:
0.1
Change: In real time
Value Range:
0.01s to 600.00s
Description
When the output current of the AC drive is lower than or equal to F8‑34 (Zero
current detection level) for a period exceeding F8‑35 (Zero current detection
delay), the DO outputs an active signal.
F8-36
Output overcurrent threshold
Address:
0xF824
Min.:
0
Unit:
%
Max.: 300 Data type: UInt16
Default:
200
Change: In real time
Value Range:
0.0% to 300.0%
Description
When the output current of the AC drive is higher than F8‑36 (Output current
threshold) for a period exceeding F8‑37 (Output overcurrent detection delay), the
DO outputs an active signal.
F8-37
Software overcurrent detection delay
Address:
0xF825
Min.:
0
Unit:
s
Max.: 600 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0.00s to 600.00s
Description
When the output current of the AC drive is higher than F8‑36 (Output current
threshold) for a period exceeding F8‑37 (Output overcurrent detection delay), the
DO outputs an active signal.