Parameter Groups
‑234‑
0.0% to 300.0%
Description
When the output current of the AC drive is lower than or equal to F8‑34 (Zero
current detection level) for a period exceeding F8‑35 (Zero current detection
delay), the DO outputs an active signal.
F8-35
Zero current detection delay
Address:
0xF823
Min.:
0.01
Unit:
s
Max.: 600 Data type: UInt16
Default:
0.1
Change: In real time
Value Range:
0.01s to 600.00s
Description
When the output current of the AC drive is lower than or equal to F8‑34 (Zero
current detection level) for a period exceeding F8‑35 (Zero current detection
delay), the DO outputs an active signal.
F8-36
Output overcurrent threshold
Address:
0xF824
Min.:
0
Unit:
%
Max.: 300 Data type: UInt16
Default:
200
Change: In real time
Value Range:
0.0% to 300.0%
Description
When the output current of the AC drive is higher than F8‑36 (Output current
threshold) for a period exceeding F8‑37 (Output overcurrent detection delay), the
DO outputs an active signal.
F8-37
Software overcurrent detection delay
Address:
0xF825
Min.:
0
Unit:
s
Max.: 600 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0.00s to 600.00s
Description
When the output current of the AC drive is higher than F8‑36 (Output current
threshold) for a period exceeding F8‑37 (Output overcurrent detection delay), the
DO outputs an active signal.