Parameter Groups
‑233‑
Value Range:
0.0% to 100.0%
Description
Detection width 1 of frequency reach = F0‑10 (Maximum frequency) x F8‑31;
Frequency detection range = F8‑30 (Detection value 1 of frequency reach) ‑ F8‑31
(Detection width 1 of frequency reach) x F0‑10 (Maximum frequency) to F8‑30
(Detection value 1 of frequency reach) + F8‑31 (Detection width 1 of frequency
reach) x F0‑10 (Maximum frequency)
F8-32
Detection value 2 for frequency reach
Address:
0xF820
Min.:
0
Unit:
Hz
Max.: F0‑10 Data type: UInt16
Default:
50
Change: In real time
Value Range:
0.00 Hz to value of F0‑10
Description
When the running frequency of the AC drive is in the frequency detection range,
the DO outputs an active signal. The valid range is from 0.00 Hz to F0‑10
(Maximum frequency).
F8-33
Detection width 2 of frequency reach
Address:
0xF821
Min.:
0
Unit:
%
Max.: 100 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0.0% to 100.0%
Description
Detection width 2 of frequency reach = F0‑10 (Maximum frequency) x F8‑33;
Frequency detection range = F8‑32 (Detection value 2 of frequency reach) ‑ F8‑33
(Detection width 2 of frequency reach) x F0‑10 to F8‑32 (Detection value 2 of
frequency reach) + F8‑33 (Detection width 2 of frequency reach) x F0‑10
F8-34
Zero current detection level
Address:
0xF822
Min.:
0
Unit:
%
Max.: 300 Data type: UInt16
Default:
5
Change: In real time
Value Range: