Parameter Groups
232
Max.: F0‑10 Data type: UInt16
Default:
50
Change: In real time
Value Range:
0.00 Hz to value of F0‑10
Description
When the running frequency is higher than the frequency detection value (FDT2),
the DO outputs an active signal. When the running frequency is lower than the
result of frequency detection value (FDT2) minus frequency detection hysteresis
(FDT2), the DO outputs an inactive signal. The valid range is from 0.00 Hz to F0‑10
(Maximum frequency).
F8-29
Frequency detection hysteresis (FDT2)
Address:
0xF81D
Min.:
0
Unit:
%
Max.: 100 Data type: UInt16
Default:
5
Change: In real time
Value Range:
0.0% to 100.0%
Description
Frequency detection hysteresis (FDT2) = F8‑28 x F8‑29 When the running
frequency is higher than F8‑28, the DO outputs an active signal. When the running
frequency is lower than a specific value (F8‑28 F8‑28 x F8‑29), the DO outputs an
inactive signal.
F8-30
Detection value 1 for frequency reach
Address:
0xF81E
Min.:
0
Unit:
Hz
Max.: F0‑10 Data type: UInt16
Default:
50
Change: In real time
Value Range:
0.00 Hz to value of F0‑10
Description
When the running frequency of the AC drive is in the frequency detection range,
the DO outputs an active signal. The valid range is 0.00 Hz to F0‑10 (Maximum
frequency).
F8-31
Detection width 1 of frequency reach
Address:
0xF81F
Min.:
0
Unit:
%
Max.: 100 Data type: UInt16
Default:
0
Change: In real time