Parameter Groups
‑231‑
Max.: F0‑10 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0.00 Hz to value of F0‑10
Description
This function is used to switch the acceleration/deceleration time based on the
running frequency range when the AC drive is running. This function is active
when the DI is not allocated with function 16 (acceleration/deceleration time
selection terminal 1) or 17 (acceleration/deceleration time selection terminal 2).
The valid range is from 0.00 Hz to F0‑10 (Maximum frequency).
F8-26
Switchover frequency of deceleration time 1 and deceleration time 2
Address:
0xF81A
Min.:
0
Unit:
Hz
Max.: F0‑10 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0.00 Hz to value of F0‑10
Description
This function is used to switch the acceleration/deceleration time based on the
running frequency range when the AC drive is running. This function is active
when the DI is not allocated with function 16 (acceleration/deceleration time
selection terminal 1) or 17 (acceleration/deceleration time selection terminal 2).
The valid range is from 0.00 Hz to F0‑10 (Maximum frequency).
F8-27
Set highest priority to jog function
Address:
0xF81B
Min.:
0
Unit:
‑
Max.: 1 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0: Disabled
1: Enabled
Description
This parameter defines whether to set the highest priority to the terminal jog
function. When F8‑27 is set to 1, and any of F4‑00 to F4‑09 is set to 4 (forward jog)
or 5 (reverse jog), the AC drive enters the jog running status immediately.
F8-28
Frequency detection value (FDT2)
Address:
0xF81C
Min.:
0
Unit:
Hz