Parameter Groups
‑134‑
Ones (position): Flux closed loop in torque control mode
0: Disabled
1: Enabled
Tens (position): Flux closed loop in speed control mode
0: Disabled
1: Enabled
Hundreds (position): Torque upper limit and torque linearity in speed control
mode
0: Disabled
1: Enabled
Description
F2-56
AC drive output current upper limit
Address:
0xF238
Min.:
0
Unit:
%
Max.: 170 Data type: UInt16
Default:
150
Change:
At stop
Value Range:
0.0% to 170.0%
Description
2.4 F3 V/f Control Parameters
F3-00
V/f curve setting
Address:
0xF300
Min.:
0
Unit:
‑
Max.: 11 Data type: UInt16
Default:
0
Change:
At stop
Value Range:
0: Linear V/f curve
1: Multi‑point V/f curve
2: Square V/f curve
3: 1.2‑power V/f curve
4: 1.4‑power V/f curve
6: 1.6‑power V/f curve
8: 1.8‑power V/f curve
10: V/f complete separation mode
11: V/f half separation mode
Description