Function Application
‑616‑
Figure 3‑67 Detection of output current limit violation
Related parameters
Para.
No.
Function Default
Value Range Description
F8‑36
Output overcurrent
threshold
200.0%
0.0% (no detection)
0.1% to 300.0% (rated
motor current)
The DO terminal outputs the active signal when the
output current of the AC drive remains above F8‑36
(output current threshold) for a period greater than
the value of F8‑37 (output overcurrent detection
delay).
F8‑37
Output overcurrent
detection delay
0.00s 0.00s to 600.00s
3.5.3.3 Detection Level of Current
The DO terminal outputs the active signal when the output current of the AC drive is
within the range of "Detection level of current 1±Detection width of current 1 x Rated
motor current".
The AC drive supports two sets of current detection levels and current detection
widths. The following figure shows the function.