Parameter Groups
‑323‑
0: Digital setting (A0‑03)
1: AI1
2: AI2
3: AI3
4: Pulse reference (DI5)
5: Communication setting (1000H)
6: Min. (AI1, AI2)
7: Max. (AI1, AI2)
Description
This parameter is used to set the torque setting source. Eight torque setting
sources are available.
A0-03
Torque digital setting
Address:
0xA003
Min.:
‑200
Unit:
%
Max.: 200 Data type: Int16
Default:
100
Change: In real time
Value Range:
‑200.0% to +200.0%
Description
This parameter defines digital setting of the torque in torque control mode. The
torque reference is a relative value. The value 100.0% corresponds to the rated
motor torque. Check U0‑06 to obtain the motor output torque, and the value
100% corresponds to the rated motor torque. The value ranges from‑ 200.0% to
+200.0%.
When the parameter value is positive, the AC drive runs in the forward direction.
When the parameter value is negative, the AC drive runs in the reverse direction.
A0-04
Torque filter time
Address:
0xA004
Min.:
0
Unit:
s
Max.: 5 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0.000s to 5.000s
Description
This parameter specifies the torque filter time.
A0-05
Speed limit digital setting
Address:
0xA005
Min.:
‑120
Unit:
%