EasyManua.ls Logo

Inovance MD500-PLUS Series - 3.5.1 Jog Running

Inovance MD500-PLUS Series
718 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Function Application
‑605‑
Parameters
Para.
Function
Default Value Range
Description
F0‑02
Command source
selection
0
0: Operating panel control
1: Terminal I/O control
2: Communication control
F0‑25
Acceleration/
Deceleration time
base frequency
1
0: Max. frequency (F0‑10)
1: Target frequency
2: 100 Hz
F7‑01
MF.K key function
selection
0
0: MF.K key disabled
1: Switchover between
operating panel control and
remote control (terminal I/O
control or communication
control)
2: Switchover between forward
and reverse run
3: Forward jog
4: Reverse jog
F8‑00
Jog frequency
2.00 Hz
0 to the maximum frequency
(F0‑10)
F8‑01
Jog acceleration
time
20.0s 0.0s to 6500.0s
F8‑02
Jog deceleration
time
20.0s 0.0s to 6500.0s
F8‑13 Reverse run
control
0
0: Reverse running allowed
1: Reverse running inhibited
F8‑27
Set highest
priority to jog
function
0
0: Disabled
1: Enabled
Example
In the following example, the operating panel is used as the jog command source to
illustrate how to set the parameters for jog running.
Table 3–30 Parameter settings for jog running through the LED operation panel
Step
Forward jog
Reverse jog
1
Set F7‑01 to 3 to assign the MF.K
key with forward jog.
Set F7‑01 to 4 to assign the MF.K
key with reverse jog.
Set F8‑13 (reverse run control) to 0
to allow reverse run.
2
Set F0‑02 (command source
selection) to 0 to select the
operating panel as the command
source.
Set F0‑02 (command source
selection) to 0 to select the
operating panel as the command
source.

Table of Contents

Other manuals for Inovance MD500-PLUS Series

Related product manuals