Parameter Groups
‑383‑
Default:
8
Change: In real time
Value Range:
‑10.000 V to +10.000 V
Description
When analog voltage correction is conducted on AI1, a correction curve is
obtained based on two points. Each point corresponds to a measured voltage and
a displayed voltage. The measured voltage is the voltage measured using a meter,
and the displayed voltage is the AI1 voltage before correction (U0‑21).
AC-03
AI1 displayed voltage 2
Address:
0xAC03
Min.:
‑10
Unit:
V
Max.: 10 Data type: Int16
Default:
8
Change: In real time
Value Range:
‑10.000 V to +10.000 V
Description
When analog voltage correction is conducted on AI1, a correction curve is
obtained based on two points. Each point corresponds to a measured voltage and
a displayed voltage. The measured voltage is the voltage measured using a meter,
and the displayed voltage is the AI1 voltage before correction (U0‑21).
AC-04
AI2 measured voltage 1
Address:
0xAC04
Min.:
‑10
Unit:
V
Max.: 10 Data type: Int16
Default:
2
Change: In real time
Value Range:
‑10.000 V to 10.000 V
Description
When analog voltage correction is conducted on AI2, a correction curve is
obtained based on two points. Each point corresponds to a measured voltage and
a displayed voltage. The measured voltage is the voltage measured using a meter,
and the displayed voltage is the AI2 voltage before correction (U0‑22).
AC-05
AI2 displayed voltage 1
Address:
0xAC05
Min.:
‑10
Unit:
V
Max.: 10 Data type: Int16
Default:
2
Change: In real time
Value Range: