Parameter Groups
‑144‑
Default:
5
Change:
At stop
Value Range:
0–50
Description
The running frequency may increase when overvoltage stall suppression is
enabled. This parameter limits the increase of the running frequency.
F3-27
Slip compensation time constant
Address:
0xF31B
Min.:
0.1
Unit:
Hz
Max.: 10 Data type: UInt16
Default:
0.5
Change: In real time
Value Range:
0.1 Hz to 10.0 Hz
Description
This parameter defines the time constant of the slip compensation frequency. The
larger the time constant is, the more stable the frequency of the slip
compensation is, and the less the frequency is affected by load disturbance and
noise. However, the response to load changes will be slower.
F3-28
V/f parameter setting inertia coefficient
Address:
0xF31C
Min.:
0
Unit:
‑
Max.: 10 Data type: UInt16
Default:
0.1
Change:
At stop
Value Range:
0.00 to 10.00
Description
F3-29
Minimum motoring torque current
Address:
0xF31D
Min.:
10
Unit:
‑
Max.: 100 Data type: UInt16
Default:
50
Change:
At stop
Value Range:
10 to 100
Description