Parameter Groups
186
16: AI1 > AI2
17: Frequency upper limit reached
18: Frequency lower limit reached (operation related)
19: Undervoltage status output
20: Communication setting
21: Reserved
22: Reserved
23: Zero‑speed running 2 (at stop)
24: Accumulative power‑on time reached
25: Frequency‑level detection FDT2 output
26: Frequency 1 reach output
27: Frequency 2 reach output
28: Current 1 reach output
29: Current 2 reach output
30: Timing reach output
31: AI1 input limit exceeded
32: AC drive output load loss
33: Reverse running
34: Zero current status
35: Module temperature reached
36: Output current limit exceeded
37: Frequency lower limit reached (having output at stop)
38: Alarm output (direct output at fault or alarm)
39: Current over‑temperature pre‑warning
40: Current running time reached
41: Fault output 2
42: Fault output 3
Description
This parameter is used to set the relay terminal function of the expansion card.
0: No output
The output terminal has no function.
1: Running
When the AC drive is running with output frequency (can be 0), the terminal
outputs an active signal.
2: Fault output (stop upon fault)
When the AC drive stops upon fault, an active signal is output.
3: Frequency‑level detection FDT1 output
When the running frequency is higher than the detected value, the DO outputs an
active signal. When the running frequency is lower than the result of the detected
value minus the FDT hysteresis value (F8‑19 x F8‑20), the active signal is canceled.