Parameter List
‑18‑
Parame
ter
Address Name Value Range Default Unit Change
Method
Page
F3‑00 0xF300 V/f curve setting 0: Linear V/f curve
1: Multi‑point V/f curve
2: Square V/f curve
3: 1.2‑power V/f curve
4: 1.4‑power V/f curve
6: 1.6‑power V/f curve
8: 1.8‑power V/f curve
10: V/f complete separation
mode
11: V/f half separation mode
0 ‑ At stop "
F3‑00
"
on
page 134
F3‑01 0xF301 Torque boost 0.0% to 30.0% 0 % In real time "
F3‑01
"
on
page 135
F3‑02 0xF302 Cutoff frequency
of torque boost
0.00 Hz to F0‑10 50 Hz At stop "
F3‑02
"
on
page 136
F3‑03 0xF303 Multi‑point V/f
frequency 1
0.00 Hz to F3‑05 0 Hz At stop "
F3‑03
"
on
page 136
F3‑04 0xF304 Multi‑point V/f
voltage 1
0.0% to 100.0% 0 % At stop "
F3‑04
"
on
page 136
F3‑05 0xF305 Multi‑point V/f
frequency 2
F3‑03 to F3‑07 0 Hz At stop "
F3‑05
"
on
page 137
F3‑06 0xF306 Multi‑point V/f
voltage 2
0.0% to 100.0% 0 % At stop "
F3‑06
"
on
page 137
F3‑07 0xF307 Multi‑point V/f
frequency 3
F3‑05 to F1‑04 0 Hz At stop "
F3‑07
"
on
page 137
F3‑08 0xF308 Multi‑point V/f
voltage 3
0.0% to 100.0% 0 % At stop "
F3‑08
"
on
page 137
F3‑09 0xF309 V/f slip
compensation
gain
0.0% to 200.0% 0 % In real time "
F3‑09
"
on
page 138
F3‑10 0xF30A V/f over‑excitation
gain
0–200 64 ‑ In real time "
F3‑10
"
on
page 138
F3‑11 0xF30B V/f oscillation
suppression gain
0–100 0 ‑ In real time "
F3‑11
"
on
page 138
F3‑12 0xF30C Oscillation
suppression gain
mode
0: Inactive
1: Reserved
2: Reserved
3: Active
3 ‑ At stop "
F3‑12
"
on
page 138
F3‑13 0xF30D Voltage source for
V/f separation
0: Digital setting (F3‑14)
1: AI1
2: AI2
3: AI3
4: Pulse reference (DI5)
5: Multi‑reference
6: Simple PLC
7: PID
8: Communication (1000H)
0 ‑ In real time "
F3‑13
"
on
page 139