Parameter Groups
‑190‑
39: Motor overtemperature
The terminal outputs an active signal when the motor temperature reaches the
value of F9‑58 (Motor overtemperature pre‑warning threshold). You can check the
motor temperature using U0‑34.
40: Current running time reached
The terminal outputs an active signal when the current operation time of the AC
drive is longer than the value of F8‑53 (current running time threshold).
41: Fault output 2
When a fault occurs on the AC drive (undervoltage excluded), the DO terminal
outputs an active signal.
42: Fault output 3
When a fault occurs on the AC drive, the DO terminal outputs an active signal.
43 to 51: Reserved
F5-02
Control board relay 1 function selection (T/A1-T/B1-TC1)
Address:
0xF502
Min.:
0
Unit:
‑
Max.: 51 Data type: UInt16
Default:
2
Change: In real time
Value Range:
0: No output
1: Running
2: Fault output (stop upon fault)
3: Frequency‑level detection FDT1 output
4: Frequency reached
5: Zero speed running (no output at stop)
6: Motor overload pre‑warning
7: AC drive overload pre‑warning
8: Set count value reached
9: Designated count value reached
10: Length reached
11: PLC cycle completed
12: Accumulative running time reached
13: Frequency limited
14: Torque limited
15: Ready for run