Parameter Groups
‑203‑
0: Running frequency (100.0% corresponding to the maximum frequency F0‑10)
1: Frequency reference
2: Output current (100.0% corresponding to 2 times the rated motor current)
3: Motor output torque (100.0% corresponding to 2 times the rated motor torque)
(absolute value, percentage of the rated motor torque)
4: Output power (100.0% corresponding to 2 times the rated motor power)
5: Output voltage (100.0% corresponding to 1.2 times the rated motor voltage)
6: Pulse input (100.0% corresponding to 100.0 kHz)
7: AI1 (100.0% corresponding to 10 V)
8: AI2 (100.0% corresponding to 10 V)
9: AI3 (100.0% corresponding to 10 V)
10: Length (100.0% corresponding to FB‑05)
11: Count value (100.0% corresponding to FB‑08)
12: Communication setting (100.0% corresponding to the AO communication
setting)
13: Motor speed (100.0% corresponding to the maximum frequency F0‑10)
14: Output current (100.0% corresponding to 1000.0 A)
15: Output voltage (100.0% corresponding to 1000.0 V)
16: Motor output torque (100.0% corresponding to 2 times the rated motor torque
in one direction; 50% corresponding to 2 times the rated motor torque in the
other direction)
(actual value, percentage of the rated motor torque)
19: Taper output
20: Roll diameter output (100.0% corresponding to the maximum roll diameter
B0‑08)
21: Tension output (100.0% corresponding to the maximum tension B1‑02)
22: Encoder feedback frequency (100.0% corresponding to the maximum
frequency F0‑10)
F5-09
Maximum FMP output frequency
Address:
0xF509
Min.:
0.01
Unit:
kHz
Max.: 100 Data type: UInt16
Default:
50
Change: In real time
Value Range:
0.01 kHz to 100.00 kHz
Description
This parameter indicates the maximum frequency (0.01 kHz to 100.00 kHz) of the
FMP terminal output pulse.
F5-10
AO1 zero offset coefficient
Address:
0xF50A