Parameter Groups
‑211‑
Description
The sum of F6‑08 (Time proportion of S‑curve start segment) and F6‑09 (Time
proportion of S‑curve end segment) must be less than or equal to 100%.
F6-09
Time proportion of S-curve end segment
Address:
0xF609
Min.:
0
Unit:
%
Max.: 70 Data type: UInt16
Default:
30
Change:
At stop
Value Range:
0.0% to 70.0%
Description
The sum of F6‑08 (Time proportion of S‑curve start segment) and F6‑09 (Time
proportion of S‑curve end segment) must be less than or equal to 100%.
F6-10
Stop mode
Address:
0xF60A
Min.:
0
Unit:
‑
Max.: 1 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0: Decelerate to stop
1: Coast to stop
Description
0: Decelerate to stop
Upon receiving the stop command, the AC drive decreases the output frequency
to 0 based on the deceleration time and then stops.
1: Coast to stop
Upon receiving the stop command, the AC drive immediately stops output. The
motor then coasts to stop according to the mechanical inertia.
F6-11
Starting frequency of DC braking at stop
Address:
0xF60B
Min.:
0
Unit:
Hz
Max.: F0‑10 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0.00 Hz to value of F0‑10
Description
The AC drive starts DC braking when the running frequency decreases to the value
of this parameter during deceleration to stop.