Parameter Groups
‑242‑
F9-04
Overvoltage threshold
Address:
0xF904
Min.:
350
Unit:
V
Max.: 820 Data type: UInt16
Default:
820
Change: In real time
Value Range:
350.0 V to 820.0 V
Description
When the bus voltage is higher than the value of F9‑04, the AC drive reports E05.00
to E07.00.
F9-06
Output phase loss detection before startup
Address:
0xF906
Min.:
0
Unit:
‑
Max.: 1 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0: Disabled
1: Enabled
Description
It takes about several seconds to detect output phase loss during running. For
low‑frequency running applications or applications where risks exist during
startup, this function enables quick detection of output phase loss during startup.
However, it is not suitable for applications that have strict requirements on
startup time.
F9-07
Detection of software short-circuited to ground
Address:
0xF907
Min.:
0
Unit:
‑
Max.: 3 Data type: UInt16
Default:
1
Change:
At stop
Value Range:
0: No detection
1: Detection before power‑on
2: Detection before running
3: Detection before power‑on and running
Description
F9-08
Braking unit applied voltage
Address:
0xF908
Min.:
200
Unit:
V