Parameter Groups
‑298‑
Description
FC‑18 to FC‑49 respectively define the running time and acceleration and
deceleration time of each of the 16 multi‑speed references. The running time of
each reference is the sum of acceleration or deceleration time and running time
at constant speed and target frequency.
FC-42
Running time of speed reference 12 set by simple PLC
Address:
0xFC2A
Min.:
0
Unit:
s (h)
Max.: 6553.5 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0.0s (h) to 6553.5s (h)
Description
FC‑18 to FC‑49 respectively define the running time and acceleration and
deceleration time of each of the 16 multi‑speed references. The running time of
each reference is the sum of acceleration or deceleration time and running time
at constant speed and target frequency.
FC-43
Acceleration/deceleration time of speed reference 12 set by simple PLC
Address:
0xFC2B
Min.:
0
Unit:
‑
Max.: 3 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0: Group 1 acceleration/deceleration time (F0‑17 and F0‑18)
1: Group 2 acceleration/deceleration time (F8‑03 and F8‑04)
2: Group 3 acceleration/deceleration time (F8‑05 and F8‑06)
3: Group 4 acceleration/deceleration time (F8‑07 and F8‑08)
Description
FC‑18 to FC‑49 respectively define the running time and acceleration and
deceleration time of each of the 16 multi‑speed references. The running time of
each reference is the sum of acceleration or deceleration time and running time
at constant speed and target frequency.
FC-44
Running time of speed reference 13 set by simple PLC
Address:
0xFC2C
Min.:
0
Unit:
s (h)
Max.: 6553.5 Data type: UInt16
Default:
0
Change: In real time
Value Range: