Parameter Groups
‑301‑
FC-50
PLC running time unit
Address:
0xFC32
Min.:
0
Unit:
‑
Max.: 1 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0: s (second)
1: h (hour)
Description
This parameter defines the unit of the PLC running time for each speed.
FC-51
Multi-reference 0 setting mode
Address:
0xFC33
Min.:
0
Unit:
‑
Max.: 6 Data type: UInt16
Default:
0
Change: In real time
Value Range:
0: Multi‑reference 0 (FC‑00)
1: AI1
2: AI2
3: AI3
4: Pulse reference (DI5)
5: PID
6: Preset frequency (F0‑08 that can be changed by pressing UP or DOWN key)
Description
Multi‑reference 0 can be selected through seven ways, including digital setting,
analog input, pulse frequency, PID, and preset frequency.
0: Multi‑reference 0 (FC‑00)
The frequency reference of multi‑reference 0 is set by FC‑00.
1: AI1
The frequency reference of multi‑reference 0 is set by AI1.
2: AI2
The frequency reference of multi‑reference 0 is set by AI2.
3: AI3
The frequency reference of multi‑reference 0 is set by AI3 input.
4: Pulse reference (DI5)
The frequency reference of multi‑reference 0 is set by pulse frequency.
5: PID
The frequency reference of multi‑reference 0 is set by PID.
6: Preset frequency (F0‑08)
The frequency reference of multi‑reference 0 is set by F0‑08 (preset frequency).