Function Application
496
Para. Name
Value
Description
F4‑11
Terminal control
mode
0
Two‑wire mode 1
F4‑00
DI1 function
selection
1
Forward run (FWD)
F4‑01
DI2 function
selection
2
Reverse run (REV)
In this mode, When SW1 is closed and SW2 is open, the motor runs in the forward
direction. When SW1 is open and SW2 is closed, the motor runs in the reverse
direction. When SW1 and SW2 are both open or closed, the motor stops, as shown in
the following figure.
Figure 3‑2 Wiring and parameter settings for two‑wire mode 1
Figure 3‑3 Timing diagram of two‑wire mode 1 (normal condition)