Function Application
‑529‑
Para.
Function
Default Value Range
Description
F6‑10
Stop mode
0
0: Decelerate
to stop
1: Coast to
stop
0: Decelerate to stop
After the stop command takes
effect, the AC drive decreases the
output frequency to 0 based on
the deceleration time and stops.
1: Coast to stop
After the stop command takes
effect, the AC drive immediately
stops output. Then, the motor
coasts to stop following
mechanical inertia.
F6‑11
Start frequency
of DC braking at
stop
0.00 Hz 0.00 Hz to F0‑
10 (Maximum
frequency)
In a decelerate‑to‑stop process,
the AC drive starts DC braking
when the running frequency drops
to this frequency.
F6‑12
Waiting time of
DC braking at
stop
0.0s 0.0s to 100.0s
When the running frequency
decreases to the start frequency of
DC braking at stop, the AC drive
stops output for a period of time
and then starts DC braking. Such
delay is intended to prevent faults
such as overcurrent from occurring
when DC braking starts at a high
speed.
F6‑13
DC braking
current at stop
0% 0% to 150%
A greater DC braking current at
stop indicates a greater braking
force. 100% corresponds to the
rated motor current. The upper
limit of the DC braking current is
80% the rated current of the AC
drive by default.
The maximum upper limit can be
set to 135% of the rated current of
the AC drive by F6‑35.
F6‑14
DC braking time
at stop
0.0s 0.0s to 100.0s
This parameter specifies the hold
time of DC braking. If this
parameter is set to 0, DC braking is
disabled.