Para.
Function
Default Value Range
Description
F5‑10 AO1 zero
offset
coefficient
0.0% ‑100.0% to
+100.0%
On the AO curve, if b indicates zero
offset, k indicates gain, and X
indicates standard output, the actual
output Y is as follows: Y = kX + b.
The zero offset coefficient 100% of
AO1 and AO2 corresponds to 10 V (or
20 mA). The standard output refers to
the value corresponding to the analog
output of 0 V to 10 V (or 0 mA to 20
mA) with no zero offset or gain
adjustment.
Zero offset = Zero offset coefficient x
10 V (or 20 mA)
The AC drive supports two AOs,
namely, AO1 and AO2. AO1 and AO2
can be used to indicate the internal
running parameters in the analog
mode. The indicated parameters are
defined by F5‑07 and F5‑‑08.
F5‑11
AO1 gain 1.00 –10.00 to +10.00
F5‑12 AO2 zero
offset
coefficient
0.0% ‑100.0% to
+100.0%
On the AO curve, if b indicates zero
offset, k indicates gain, and X
indicates standard output, the actual
output Y is as follows: Y = kX + b.
The zero offset coefficient 100% of
AO1 and AO2 corresponds to 10 V (or
20 mA). The standard output refers to
the value corresponding to the analog
output of 0 V to 10 V (or 0 mA to 20
mA) with no zero offset or gain
adjustment.
Zero offset = Zero offset coefficient x
10 V (or 20 mA)
The AC drive supports two AOs,
namely, AO1 and AO2. AO1 and AO2
can be used to indicate the internal
running parameters in the analog
mode. The indicated parameters are
defined by F5‑07 and F5‑‑08.