Function Application
‑570‑
Table 3–23 Parameters of V/f separation curve
Para.
Function
De
fault
Value Range
Description
F3‑13
Voltage
source for
V/f
separation
0
0: Digital
setting (F3‑14)
1: AI1
2: AI2
3: AI3
4: Pulse
reference (DI5)
5: Multi‑
reference
6: Simple PLC
7: PID
8:
Communica
tion
Note: The
value of
100.0%
corresponds
to the rated
motor voltage.
This parameter is used to set the target
voltage in the voltage and frequency
separation mode.
0: Digital setting (F3‑14)
F3‑14 (voltage digital setting for V/f
separation) can be used to set the V/f
separation voltage.
1: AI1
The V/f separation voltage is input through
AI1 by current or voltage signal. The
frequency is calculated according to the set
AI curve.
2: AI2
The V/f separation voltage is input through
AI2 by current or voltage signal. The
frequency is calculated according to the set
AI curve.
3: AI3
The V/f separation voltage is input through
AI3 by current or voltage signal. The
frequency is calculated according to the set
AI curve.
Contin
ued
Continued
Con
tinu
ed
Continued 4: Pulse reference (DI5)
The V/f separation voltage is set through
DI5. The frequency is calculated based on
the curve of relationship between the pulse
frequency and running frequency.
5: Multi‑reference
When multi‑reference is configured as the
source for V/f separation voltage, setpoints
can be configured by grouping different DI
states. The four multi‑reference terminals
can provide 16 state combinations,
corresponding to 16 reference values
(percentage x maximum frequency) of
parameters in group FC.