Function Application
598
Figure 3‑50 Working principle of wobble
Table 3–29 Related parameters
Para.
No.
Function Default
Value Range Description
Fb‑00
Wobble setting mode
0
0: Relative to central
frequency
1: Relative to max.
frequency
0: Relative to central frequency (F0‑07: final
frequency reference setting selection): It is a variable
wobble system and the wobble changes with the
central frequency (frequency reference).
1: Relative to max. frequency (F0‑10: max. frequency):
It is a fixed wobble system and the wobble is
calculated based on the maximum frequency.
Fb‑01
Wobble amplitude
0.0% 0.0% to 100.0%
When Fb‑01 is set to 0, the wobble function is
disabled.
Fb‑02
Jump frequency
amplitude
0.0% 0.0% to 50.0%
Used to determine the wobble amplitude and jump
frequency.
The wobble running frequency is limited by the
frequency upper limit and frequency lower limit.
Fb‑03
Wobble cycle
10.0s 0.1s to 3000.0s
Time of a complete wobble cycle.
Fb‑04
Triangular wave rise
time coefficient
50.0% 0.1% to 100.0%
Ratio (in percentage) of triangular wave rise time to
wobble cycle (Fb‑03)
1. Wobble amplitude calculation
When Fb‑00 is set to 0 (relative to central frequency), wobble amplitude AW is
calculated according to the following formula: AW = Frequency reference source
(F0‑07) x Wobble amplitude (Fb‑01).