Function Application
‑622‑
Para. Name De
fault
Value Range
Description
B0‑01
Winding mode
0
0: Winding This parameter is used together
with function 58 of the DI
(winding/unwinding switchover
terminal) to determine the
winding mode. When the winding/
unwinding switchover terminal is
disabled, the winding mode is the
same as that set by this
parameter. When the winding/
unwinding switchover terminal is
enabled, the winding mode is
opposite to that set by this
parameter.
1: Unwinding
Para. Name De
fault
Value Range
Description
F0‑09
Running direction
selection
0
0: Default
direction
Set this parameter properly to
ensure normal winding/
unwinding. Determine the
direction as follows.
1: Reverse of
the default
direction
Judging the running direction
When B0‑00 is set to 1 (tension control mode disabled), the AC drive runs in speed
control mode and its running direction should be the same as the target winding
direction (opposite to the target unwinding direction). Otherwise, change the
parameter to correct the direction. Check the running direction according to the
following figure.