Function Application
672
Parameters
Para.
Function
Default Value Range
Description
F9‑48
Fault
protection
action
selection 1
10050
Ones position: E11
0: Coast to stop
1: Decelerate to
stop
2: Fault reset
4: Alarm
5: Canceled
Tens position: E12
(same as the ones)
Hundreds position:
E13 (same as the
ones)
Thousands position:
E14
0: Coast to stop
Ten thousands
position: E15
0: Coast to stop
1: Decelerate to
stop
3: Electromagnetic
shorting
4: Alarm
5: Canceled
The fault protection actions
are set through the ones, tens,
hundreds, thousands, and ten
thousands positions of this
parameter.
0: Coast to stop
The AC drive coasts to stop.
1: Decelerate to stop
The AC drive decelerates to
stop.
2: Fault reset
The AC drive will be restarted
upon a fault.
3: Electromagnetic shorting
The AC drive enters the
electromagnetic shorting
state.
4: Alarm
The AC drive continues to run.
5: Canceled
The fault is ignored.
F9‑49
Fault
protection
action
selection 2
00050
Ones position: E16
0: Coast to stop
1: Decelerate to
stop
4: Alarm
5: Canceled
Tens position: E17
(same as the ones)
Hundreds position:
E18
0: Coast to stop
Thousands position:
E19
0: Coast to stop
3: Electromagnetic
shorting
4: Alarm
5: Canceled
Ten thousands: E20
(same as the
thousands)
Same as F9‑48