Function Application
674
Para.
Function
Default Value Range
Description
F9‑52
Fault
protection
action
selection 5
00101
Ones position: E31
0: Coast to stop
1: Decelerate to
stop
4: Alarm
5: Canceled
Tens position: E40
0: Coast to stop
2: Fault reset
Hundreds position:
E41 (same as the
ones)
Thousands position:
E42
0: Coast to stop
1: Decelerate to
stop
2: Fault reset
3: Electromagnetic
shorting
4: Alarm
5: Canceled
Ten thousands
position: E43
0: Coast to stop
1: Decelerate to
stop
3: Electromagnetic
shorting
4: Alarm
5: Canceled
Same as F9‑48
F9‑53
Fault
protection
action
selection 6
05500
Ones position: E45
0: Coast to stop
1: Decelerate to
stop
4: Alarm
5: Canceled
Tens position: E60
(same as the ones)
Hundreds position:
E61 (same as the
ones)
Thousands position:
E62
0: Coast to stop
5: Canceled
Ten thousands:
Reserved
5: Canceled
Same as F9‑48