Function Application
684
Para.
Function Basic Unit Description
U0‑43
DI function
state display 1
(function 01‑40)
1
This parameter indicates whether terminal
functions 1 to 40 are valid. There are five LEDs
on the operating panel, representing the
following functions from right to left:
functions 1 to 8, 9 to 16, 17 to 24, 25 to 32, and
33 to 40. Each LED corresponds to eight
functions, as shown in the following figure.
The LEDs indicate states of DI functions. ON
indicates high level, and OFF indicates low
level.
4
1
2
6
5 3
7
8
U0‑44
DI function
state display 2
(functions 41 to
80)
1
This parameter indicates whether terminal
functions 41 to 59 are valid. There are five
LEDs on the operating panel, representing the
following functions from right to left:
functions 41 to 48, 49 to 56, and 57 to 59. Each
LED corresponds to eight functions, as shown
in the following figure.
The LEDs indicate states of DI functions. ON
indicates high level, and OFF indicates low
level.
44
41
42
46
45 43
47
48
U0‑45
Fault subcode
1
This parameter indicates fault subcodes.
U0‑46 Inverter unit
temperature
1℃
This parameter indicates the inverter heatsink
temperature.
U0‑47
PTC channel
voltage before
correction
0.001
U0‑48
PTC channel
voltage after
correction
0.001
U0‑49
Number of
offset pulses of
position lock
1
Pulse difference between the initial position of
position lock and the current position
U0‑50
Roll diameter
1 mm
Current roll diameter