Parameter Groups
‑96‑
0: Digital setting (preset frequency (F0‑08) that can be changed by pressing UP/
DOWN, non‑retentive upon power failure)
1: Digital setting (preset frequency (F0‑08) that can be changed by pressing UP/
DOWN, retentive at power failure)
2: AI1
3: AI2
4: AI3
5: Pulse reference (DI5)
6: Multi‑reference
7: Simple PLC
8: PID
9: Communication
10: Reserved
Description
0: Digital setting (non‑retentive at power failure)
The initial value of the frequency reference is the value of F0‑08 (preset
frequency). The value can be changed by using the ▲ and ▼ keys on the
operating panel (or UP and DOWN of the multi‑function input terminal). When the
AC drive is powered on again after power failure, the set frequency reverts to the
value of F0‑08.
1: Digital setting (retentive at power failure)
The initial value of the frequency reference is the value of F0‑08 (preset
frequency). This value can be changed by using the ▲ and ▼ keys on the
operating panel (or UP and DOWN of the multi‑function input terminal). When the
AC drive is powered on again after power failure, the frequency reference is that
before the last power failure. The value set by pressing ▲/▼ or pressing UP/
DOWN is retained.
2: AI1
The frequency reference is input by current or voltage signal through the AI1. The
frequency is calculated according to the preset AI curve.
3: AI2
The frequency reference is input by current or voltage signal through the AI2. The
frequency is calculated according to the preset AI curve.
4: AI3
The frequency reference is input by current or voltage signal through the AI3
terminal. The frequency is calculated according to the preset AI curve.
5: Pulse reference (DI5)
The frequency upper limit is set through the DI5. The frequency is calculated
based on the curve of the relationship between the pulse frequency and the
setting frequency.