What to do if Inovance Controller detects overvoltage when heavy load is suddenly removed?
- RRebecca ClarkAug 31, 2025
If the Inovance Controller detects overvoltage when a heavy load is suddenly removed or during deceleration, first ensure that F3-23 (overvoltage stall enable) is enabled. If the issue persists, gradually increase the setting of F3-24/F3-25 (overvoltage stall gain, default is 30) by 10, up to a maximum of 100. Alternatively, you can gradually decrease the setting of F3-22 (overvoltage stall actuating voltage, default is 770V) by 10 V, down to a minimum of 700 V.