Goodrive300-01A-RT series integrated machine Function description
-32-
Function
code
Name
Description
Default
Modify
P00.10
Frequency set through
keypad
0.00 HzP00.03 (max. output frequency)
50.00Hz
P00.11
ACC time 1
0.03600.0s
Model
depended
P00.12
DEC time 1
0.03600.0s
Model
depended
P00.13
Running direction
0: Run at the default direction.
1: Run at the opposite direction.
2: Disable reverse running
2
P00.14
Carrier frequency
setting
1.08.0kHz
4
P00.15
Motor parameter
autotuning
0: No operation
1: Rotary autotuning
2: Static autotuning 1 (comprehensive
autotuning)
0
P00.16
AVR function selection
0: Disable
1: Valid during the whole procedure
1
P00.17
VFD type
0: G type
0
P00.18
Function parameter
restore
0: No operation
1: Restore to default value
2: Clear fault history
3: Start/stop the VFD with one click in
communication mode (compatible with the
Plot controller)
4: Start/stop the VFD with one click in
terminal mode (compatible with the Plot
controller)
Note: Though restoring to default values is
enabled, the motor parameters in P02 group
remain unchanged; P18.04, P18.28,
P18.29, P18.32, P18.33, P21.04, P21.05,
and P21.06 also remain unchanged.
0

Table of Contents