Goodrive300-01A-RT series integrated machine Function description
-40-
Function
code
Name
Description
Default
Modify
P04.07
V/F frequency point 3
of motor 1
P04.05P02.02 (rated frequency of AM 1)
/P04.05P02.16 (rated frequency of SM 1)
00.00Hz
P04.08
V/F voltage point 3 of
motor 1
0.0%110.0% (of the rated voltage of motor
1)
00.0%
P04.09
V/F slip compensation
gain of motor 1
0.0200.0%
100.0%
P04.10
Low-frequency
oscillation control
factor of motor 1
0100
10
P04.11
High-frequency
oscillation control
factor of motor 1
0100
10
P04.12
Oscillation control
threshold of motor 1
0.00HzP00.03 (max. output frequency)
30.00Hz
P04.26
Energy-saving run
0: Disable
1: Automatic energy-saving run
0
P04.33
Weakening coefficient
in constant power zone
1.001.30
1.00
P04.34
Reactive closed-loop
proportional coefficient
03000
When the SM V/F control mode is enabled,
the function code is used to set the
proportional coefficient of the reactive
current closed-loop control.
100
P04.35
Reactive closed-loop
integral coefficient
03000
When the SM V/F control mode is enabled,
the function code is used to set the integral
coefficient of the reactive current closed-loop
control.
20

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT Goodrive300-01A-RT Series and is the answer not in the manual?

INVT Goodrive300-01A-RT Series Specifications

General IconGeneral
BrandINVT
ModelGoodrive300-01A-RT Series
CategoryInverter
LanguageEnglish

Related product manuals