SECTION 8 - MICROPANEL
FORM 201.23-NM2
ISSUE DATE: 3/9/2015
8
Local / Remote Control Mode Selection
Local or Remote Control Mode allows the user to se-
lect the chilled liquid temperature control mode.
OPTIONS LOCAL / REMOTE CONTROL MODE
â—„ â–º XXXXXXXXXXXXXXXXXX
When LOCAL CONTROL mode is selected, chilled
liquid control is from the keypad of the chiller. In local
mode, a remote device can read system data, but not
reset operating parameters.
OPTIONS LOCAL / REMOTE CONTROL MODE
â—„ â–º LOCAL CONTROL
When REMOTE CONTROL mode is selected, control
of the chilled liquid setpoint is from a remote device
such as an ISN/BAS controller.
OPTIONS LOCAL / REMOTE CONTROL MODE
â—„ â–º REMOTE CONTROL
The default mode will be LOCAL.
Display Units Selection
Imperial or SI display units may be selected for data
display.
OPTIONS DISPLAY UNITS
â—„ â–º XXXXXXXXXXXXXXXXXX
The user may select system operating temperatures and
pressures to be displayed in either SI (°C, Barg) or Im-
perial units (°F, PSIG).
OPTIONS DISPLAY UNITS
â—„ â–º IMPERIAL
OPTIONS DISPLAY UNITS
â—„ â–º SI
The default mode is IMPERIAL.
System Lead/Lag Control Mode Selection
The operator may select the type of lead/lag control
desired.
OPTIONS LEAD / LAG CONTROL MODE
â—„ â–º XXXXXXXXXXXXXXXXXX
In most cases, automatic lead/lag will be selected.
When automatic lead/lag is selected, the microproces-
sor will attempt to balance run time by switching the
lead compressor whenever all compressors are shut
off. If a compressor is not able to run when the mi-
croprocessor attempts a start, the microprocessor will
select another compressor in an effort to control chilled
liquid temperature. Manual lead/lag allows selecting a
specific compressor to be the lead. If #2 is selected as
the lead in a 3 compressor chiller, the sequence will be
2, 3, and 1.
OPTIONS LEAD / LAG CONTROL MODE
â—„ â–º AUTOMATIC
The default mode will be AUTOMATIC.
Lag selections of individual systems will appear as:
OPTIONS LEAD / LAG CONTROL MODE
â—„ â–º MANUAL SYS 1 LEAD
OPTIONS LEAD / LAG CONTROL MODE
â—„ â–º MANUAL SYS 2 LEAD
OPTIONS LEAD / LAG CONTROL MODE
â—„ â–º MANUAL SYS 3 LEAD
SYSTEM 3 LEAD may be selected only on 3 and 4
compressor units.
OPTIONS LEAD / LAG CONTROL MODE
â—„ â–º MANUAL SYS 4 LEAD
SYSTEM 4 LEAD may be selected only on 4 compres-
sor units.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls York YCIV A Series and is the answer not in the manual?

Johnson Controls York YCIV A Series Specifications

General IconGeneral
BrandJohnson Controls
ModelYork YCIV A Series
CategoryChiller
LanguageEnglish

Related product manuals