JOHNSON CONTROLS
304
FORM 201.23-NM2
ISSUE DATE: 3/9/2015
SECTION 8 - MICROPANEL
TABLE 28 - BACNET AND MODBUS COMMUNICATIONS DATA MAP
8/25/2014
YCAV/YCIV
1st, 2nd Systems
REV K03G
YORK TALK 2
Micro Board: 031-02478-xxx
Item Checksum YORK P N Baud
1 13A8 031-02476-001 4800
2 3A9E 031-02476-002 4800
3 98E1 031-02476-001 4800
4 32D7 031-02476-002 4800
5 935C 031-02476-001 4800
6 1D47 031-02476-002 4800
7 98FB 031-02476-001 4800
8 n/a 031-02476-002 4800
9
10
POINT LIST CODE: S = STANDARD O = OPTIONAL N = NOT AVAILABLE
Address Scale Imper SI
POINT LIST DESCRIPTION 12345678910
P03
AV1
YT2_ S01_ P03 nviYTS01p003 SNVT_count_f (51)
ADF 1
0001 Div 10
°F °C
Setpoint ( Start command must be active to take effect)
SSSSSSSS P03
P04
AV2
YT2_ S01_ P04 nviYTS01p004 SNVT_count_f (51)
ADF 2 0002 Div 10 % % ISN Current Limit Start command must be active to take effect S S S S S S S S P04
P05
AV3
YT2_ S01_ P05 nviYTS01p005 SNVT_count_f (51)
ADF 3 0003 Div 10 % % ISN Sound Limit ( RSL Option must be enabled or this point ignored) S S S S S S S S P05
P06
AV4
YT2_ S01_ P06 nviYTS01p006 SNVT_count_f (51)
ADF 4 0004 Div 10 P06
P07
BV1
YT2_ S01_ P07 nviYTS01p007 SNVT_switch (95)
BD 1
0061 N/A
0 / 1 0 / 1 Start / Stop Command SSSSSSSS P07
P08
BV2
YT2_ S01_ P08 nviYTS01p008 SNVT_switch (95)
BD 2 0062 N/A P08
P09
BV3
YT2_ S01_ P09 nviYTS01p009 SNVT_switch (95)
BD 3 0063 N/A P09
P10
BV4
YT2_ S01_ P10 nviYTS01p010 SNVT_switch (95)
BD 4 0064 N/A 0 / 1 0 / 1 History Buffer 1 Request SSSSSSSS P10
P11
AV5
YT2_ S01_ P11 nvoYTS01p011 SNVT_count_f (51)
ADF 5 0005 X 10 °F °C Leaving Chilled Liquid Temp SSSSSSSS P11
P12
AV6
YT2_ S01_ P12 nvoYTS01p012 SNVT_count_f (51)
ADF 6 0006 X 10 °F °C Return Chilled Liquid Temp SSSSSSSS P12
P13
AV7
YT2_ S01_ P13 nvoYTS01p013 SNVT_count_f (51)
ADF 7
0007 X 10 °F °C
VSD Internal Ambient Temp SSSSSSSS
P13
P14
AV8
YT2_ S01_ P14 nvoYTS01p014 SNVT_count_f (51)
ADF 8 0008 X 10 °F °C Sys 1 Suction Temperature SSSSSSSS P14
P15
AV9
YT2_ S01_ P15 nvoYTS01p015 SNVT_count_f (51)
ADF 9 0009 X 10 °F °C Sys 1 Discharge Temperature SSSSSSSS P15
P16
AV10
YT2_ S01_ P16 nvoYTS01p016 SNVT_count_f (51)
ADF 10 0010 X10 °F °C Outside Ambient Air Temperature SSSSSSSS P16
P17
AV11
YT2_ S01_ P17 nvoYTS01p017 SNVT_count_f (51)
ADF 11 0011 X10 °F °C Sys 1 Oil Temperature SSSSSSSS P17
P18
AV12
YT2_ S01_ P18 nvoYTS01p018 SNVT_count_f (51)
ADF 12 0012 X10 PSI BAR Sys 1 Oil Pressure (gauge) SSSSSSSS P18
P19
AV13
YT2_ S01_ P19 nvoYTS01p019 SNVT_count_f (51)
ADF 13 0013 X10 PSI BAR Sys 1 Suction Pressure (gauge) SSSSSSSS P19
P20
AV14
YT2_ S01_ P20 nvoYTS01p020 SNVT_count_f (51)
ADF 14 0014 X10 PSI BAR Sys 1 Discharge Pressure (gauge) SSSSSSSS P20
P21
AV15
YT2_ S01_ P21 nvoYTS01p021 SNVT_count_f (51)
ADF 15 0015 X10 % % Sys 1 Compressor % Full Load Amps SSSSSSSS P21
P22
AV16
YT2_ S01_ P22 nvoYTS01p022 SNVT_count_f (51)
ADF 16 0016 X1 * hrs hrs Sys 1 Total Run Hours SSSSSSSS P22
P23
AV17
YT2_ S01_ P23 nvoYTS01p023 SNVT_count_f (51)
ADF 17 0017 X1 * count count Sys 1 Total Number of Starts SSSSSSSS P23
P24
AV18
YT2_ S01_ P24 nvoYTS01p024 SNVT_count_f (51)
ADF 18 0018 X 10 °F °C Sys 1 Highest Motor Temp SSSSSSSS P24
P25
AV19
YT2_ S01_ P25 nvoYTS01p025 SNVT_count_f (51)
ADF 19 0019 X 10 °F °C Sys 2 Highest Motor Temp SSSSSSSS P25
P26
AV20
YT2_ S01_ P26 nvoYTS01p026 SNVT_count_f (51)
ADF 20 0020 X 10 °F °C Sys 2 Oil Temperature SSSSSSSS P26
P27
AV21
YT2_ S01_ P27 nvoYTS01p027 SNVT_count_f (51)
ADF 21 0021 X 10 PSI BAR Sys 2 Oil Pressure (gauge) SSSSSSSS P27
P28
AV22
YT2_ S01_ P28 nvoYTS01p028 SNVT_count_f (51)
ADF 22 0022 X 10 PSI BAR Sys 2 Suction Pressure (gauge) SSSSSSSS P28
P29
AV23
YT2_ S01_ P29 nvoYTS01p029 SNVT_count_f (51)
ADF 23 0023 X 10 PSI BAR Sys 2 Discharge Pressure (gauge) SSSSSSSS P29
P30
AV24
YT2_ S01_ P30 nvoYTS01p030 SNVT_count_f (51)
ADF 24 0024 X 1 % % Sys 2 Compressor % Full Load Amps SSSSSSSS P30
P31
AV25
YT2_ S01_ P31 nvoYTS01p031 SNVT_count_f (51)
ADF 25 0025 X1 * hrs hrs Sys 2 Total Run Hours SSSSSSSS P31
P32
AV26
YT2_ S01_ P32 nvoYTS01p032 SNVT_count_f (51)
ADF 26 0026 X1 * count count Sys 2 Total Number of Starts SSSSSSSS P32
P33
AV27
YT2_ S01_ P33 nvoYTS01p033 SNVT_count_f (51)
ADF 27 0027 X1 * hz hz VSD Output Frequency SSSSSSSS P33
P34
AV28
YT2_ S01_ P34 nvoYTS01p034 SNVT_count_f (51)
ADF 28 0028 X 1 % % Sys 1 Flash Tank Feed Valve % Open OOOOOOOO P34
P35
AV29
YT2_ S01_ P35 nvoYTS01p035 SNVT_count_f (51)
ADF 29 0029 X 10 % % Sys 2 Flash Tank Feed Valve % Open OOOOOOOO P35
P36
BV5
YT2_ S01_ P36 nvoYTS01p036 SNVT_switch (95)
BD 5 0065 N/A 0 / 1 0 / 1 Chiller Run SSSSSSSS P36
P37
BV6
YT2_ S01_ P37 nvoYTS01p037 SNVT_switch (95)
BD 6 0066 N/A 0 / 1 0 / 1 Chiller Alarm ( 0 = no alarm, 1 = alarm ) SSSSSSSS P37
P38
BV7
YT2_ S01_ P38 nvoYTS01p038 SNVT_switch (95)
BD 7
0067 N/A
0 / 1 0 / 1 Evaporator Heater Status SSSSSSSS P38
P39
BV8
YT2_ S01_ P39 nvoYTS01p039 SNVT_switch (95)
BD 8 0068 N/A 0 / 1 0 / 1 Evaporator Pump Status SSSSSSSS P39
P40
BV9
YT2_ S01_ P40 nvoYTS01p040 SNVT_switch (95)
BD 9 0069 N/A 0 / 1 0 / 1 Sys 1 Compressor Run Status SSSSSSSS P40
P41
BV10
YT2_ S01_ P41 nvoYTS01p041 SNVT_switch (95)
BD 10 0070 N/A 0 / 1 0 / 1 Sys 2 Compressor Run Status SSSSSSSS P41
P42
BV11
YT2_ S01_ P42 nvoYTS01p042 SNVT_switch (95)
BD 11 0071 N/A 0 / 1 0 / 1 Sys 1 Economizer Solenoid Valve Status SSSSSSSS P42
COMMENTS
ENG
PAGE
Ref
ENG UNITS
Opt: Add p72 functionality (SCR 796)
Std. : see Elink Installation manual PN 24-10404-9 for wiring instructions
Opt
Std. : added p80,p81
Opt added p80,p81
STD- Foreign langauge enhancements
OPT Foreign langauge enhancements
Std: Add p72 functionality (SCR 796)
MODBUS
see note 3
LON SNVT Type
LON Profile
Name
Bacnet Object
Name
ENG
PAGE
Ref
SECTION 1 ELINK
BACnet
Object
Typ/Ins
N2
Metasys
C.A09.14.03
C.A09.15.03
C.A14.14.03
C.A16.15.03
Version
C.A15.14.01
C.A15.15.01
C.A15.14.03
C.A15.15.03
Revision: YCAV_YCIV BAS (Rev K_03g).xlsx Tab: YCAV and YCIV Property of Johnson Controls, York, PA Page: 1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls York YCIV A Series and is the answer not in the manual?

Johnson Controls York YCIV A Series Specifications

General IconGeneral
BrandJohnson Controls
ModelYork YCIV A Series
CategoryChiller
LanguageEnglish

Related product manuals