SECTION 6 - TECHNICAL DATA
HIGH EFFICIENCY 3-COMPRESSOR UNITS
(One Field Provided Power Supply Circuit. Field Connections to Factory
provided Terminal Block (Standard); or Individual System Breakers (Optional).
MODEL NO./NAME-
PLATE
SYSTEM 1 SYSTEM 2 SYSTEM 2 SYSTEM 3
STD. & ULTRA QUIET
COND. FANS
HIGH HEAD/STATIC
COND. FANS
TWO-SPEED COND.
FANS
STD. & ULTRA QUIET
COND. FANS
HIGH HEAD/STATIC
COND. FANS
TWO-SPEED COND.
FANS
STD. & ULTRA QUIET
COND. FANS
HIGH HEAD/STATIC
COND. FANS
TWO-SPEED COND.
FANS
YCIV
E/V
INPUT
VOLTS
(9)
INPUT
FREQ
COMP.
CONDENSER
FANS
COMP.
CONDENSER
FANS
COMP.
CONDENSER
FANS
COMP.
CONDENSER
FANS
COMP.
CONDENSER
FANS
COMP.
CONDENSER
FANS
COMP.
CONDENSER
FANS
COMP.
CONDENSER
FANS
COMP.
CONDENSER
FANS
RLA
(5)
QTY.
FLA
(EA)
RLA
(5)
QTY.
FLA
(EA)
RLA
(5)
QTY.
FLA
(EA)
RLA
(5)
QTY.
FLA
(EA)
RLA
(5)
QTY.
FLA
(EA)
RLA
(5)
QTY.
FLA
(EA)
RLA
(5)
QTY.
FLA
(EA)
RLA
(5)
QTY.
FLA
(EA)
RLA
(5)
QTY.
FLA
(EA)
0267
460 60 142 5 2.8 142 5 2.8 105 4 2.8
380 60 179 5 3.5 179 5 9.3 179 4 3.5 179 4 9.3 133 4 3.5 133 4 9.3
0287
460 60 137 5 2.8 137 5 2.8 137 5 2.8
380 60 173 5 3.5 173 5 9.3 173 5 3.5 173 5 9.3 173 4 3.5 173 4 9.3
0327
460 60 152 5 2.8 152 5 2.8 141 6 2.8
380 60 193 5 3.5 193 5 9.3 193 5 3.5 193 5 9.3 178 6 3.5 178 6 9.3
0357
460 60 181 6 2.8 181 6 2.8 139 6 2.8
380 60 229 6 3.5 229 6 9.3 229 6 3.5 229 6 9.3 176 6 3.5 176 6 9.3
YCIV
S/P
Control
KVA (7)
Unit Short Circuit
Withstand (KA)
Field Wiring & Protection Field Wiring & Protection Field Wiring Lugs
Std. & Ultra Quiet Cond. Fans High Head/High Static Fans
High Head/High Static
Fans
Two-Speed Cond. Fans
STD Terminal
Block
OPT Circuit
Breaker
Terminal
Block
(STD)
Circuit
Breaker
(OPT)
Mini-
mum Ckt.
Ampacity
(MCA) (3)
Recommend-
ed Fuse/Ckt.
Breaker
Rating (4)
Max.
Inverse
Time Ckt.
Brkr. Rat-
ing (2)
Max Dual
Element
Fuse
Size (2)
Minimum
Ckt.
Ampacity
(MCA) (3)
Recommended
Fuse/Ckt.
Breaker
Rating (4)
Max.
Inverse
Time Ckt.
Brkr. Rat-
ing (2)
Max Dual
Element
Fuse
Size (2)
Minimum
Ckt.
Ampacity
(MCA) (3)
Recommended
Fuse/Ckt.
Breaker
Rating (4)
Max.
Inverse
Time Ckt.
Brkr. Rat-
ing (2)
Max Dual
Element
Fuse
Size (2)
Lugs/
Phase
(1)
Lug Wire
Range
Lugs/
Phase
(1)
Lug Wire
Range
0287
2.4 30KA 65KA 463 600 600 600 4
#2 - 600
KCM
4
#4/0 - 500
KCM
2.4 30KA 65KA 581 700 700 700 632 800 800 800 4
#2 - 600
KCM
4
#4/0 - 500
KCM
0307
2.4 30KA 65KA 486 600 600 600 4
#2 - 600
KCM
4
#4/0 - 500
KCM
2.4 30KA 65KA 610 700 700 700 659 800 800 800 4
#2 - 600
KCM
4
#4/0 - 500
KCM
0357
2.4 30KA 65KA 528 600 600 600 4
#2 - 600
KCM
4
#4/0 - 500
KCM
2.4 30KA 65KA 667 800 800 800 728 800 800 800 4
#2 - 600
KCM
4
#4/0 - 500
KCM
0397
2.4 30KA 65KA 598 700 700 700 4
#2 - 600
KCM
4
#4/0 - 500
KCM
2.4 30KA 65KA 755 800 800 800 818 1000 1000 1000 4
#2 - 600
KCM
4
#4/0 - 500
KCM
See page 92 for Electrical Data footnotes.