JOHNSON CONTROLS
279
SECTION 8 - MICROPANEL
FORM 201.23-NM2
ISSUE DATE: 3/9/2015
8
LD10605
MANUAL OVERRIDE
KEY
MANUAL OVERRIDE KEY
Manual Overrride Key Operation
If the MANUAL OVERRIDE key is pressed during
a schedule shutdown, the STATUS display will dis-
play the message below. This indicates that the Daily
Schedule is being ignored and the chiller will start
when chilled liquid temperature allows, Remote Con-
tacts, UNIT switch and SYSTEM switches permitting.
This is a priority message and cannot be overridden by
anti-recycle messages, fault messages, etc. when in the
STATUS display mode. Therefore, do not expect to see
any other STATUS messages when in the MANUAL
OVERRIDE mode. MANUAL OVERRIDE is to only
be used in emergencies or for servicing. Manual over-
ride mode automatically disables itself after 30 min-
utes.
MANUAL OVERRIDE