JOHNSON CONTROLS
306
FORM 201.23-NM2
ISSUE DATE: 3/9/2015
SECTION 8 - MICROPANEL
TABLE 28 - BACNET AND MODBUS COMMUNICATIONS DATA MAP (CONT’D)
8/25/2014
YCAV/YCIV
3rd, 4th Systems
YORK TALK 2
Micro Board: 031-02478-xxx
POINT LIST CODE: S = STANDARD O = OPTIONAL N = NOT AVAILABLE
Address Scale Imper SI
POINT LIST DESCRIPTION 12345678910
P03
AV101
YT2_ S02_ P03 nviYTS02p003 SNVT_count_f (51)
ADF 44 0101 Div 10 P03
P04
AV102
YT2_ S02_ P04 nviYTS02p004 SNVT_count_f (51)
ADF 45 0102 Div 10 P04
P05
AV103
YT2_ S02_ P05 nviYTS02p005 SNVT_count_f (51)
ADF 46 0103 Div 10 P05
P06
AV104
YT2_ S02_ P06 nviYTS02p006 SNVT_count_f (51)
ADF 47 0104 Div 10 P06
P07
BV101
YT2_ S02_ P07 nviYTS02p007 SNVT_switch (95)
BD 30 0161 N/A P07
P08
BV102
YT2_ S02_ P08 nviYTS02p008 SNVT_switch (95)
BD 31 0162 N/A P08
P09
BV103
YT2_ S02_ P09 nviYTS02p009 SNVT_switch (95)
BD 32 0163 N/A P09
P10
BV104
YT2_ S02_ P10 nviYTS02p010 SNVT_switch (95)
BD 33 0164 N/A P10
P11
AV105
YT2_ S02_ P11 nvoYTS02p011 SNVT_count_f (51)
ADF 48 0105 X 10 °F °C Leaving Chilled Liquid Temp SSSSSSSS P11
P12
AV106
YT2_ S02_ P12 nvoYTS02p012 SNVT_count_f (51)
ADF 49 0106 X 10 °F °C Return Chilled Liquid Temp SSSSSSSS P12
P13
AV107
YT2_ S02_ P13 nvoYTS02p013 SNVT_count_f (51)
ADF 50 0107 X 10 °F °C VSD Internal Ambient Temp 2 SSSSSSSS P13
P14
AV108
YT2_ S02_ P14 nvoYTS02p014 SNVT_count_f (51)
ADF 51 0108 X 10 °F °C Sys 3 Suction Temperature SSSSSSSS P14
P15
AV109
YT2_ S02_ P15 nvoYTS02p015 SNVT_count_f (51)
ADF 52 0109 X 10 °F °C Sys 3 Discharge Temperature SSSSSSSS P15
P16
AV110
YT2_ S02_ P16 nvoYTS02p016 SNVT_count_f (51)
ADF 53 0110 X10 P16
P17
AV111
YT2_ S02_ P17 nvoYTS02p017 SNVT_count_f (51)
ADF 54 0111 X10 °F °C Sys 3 Oil Temperature SSSSSSSS P17
P18
AV112
YT2_ S02_ P18 nvoYTS02p018 SNVT_count_f (51)
ADF 55 0112 X10 PSI BAR Sys 3 Oil Pressure SSSSSSSS P18
P19
AV113
YT2_ S02_ P19 nvoYTS02p019 SNVT_count_f (51)
ADF 56 0113 X10 PSI BAR Sys 3 Suction Pressure SSSSSSSS P19
P20
AV114
YT2_ S02_ P20 nvoYTS02p020 SNVT_count_f (51)
ADF 57 0114 X10 PSI BAR Sys 3 Discharge Pressure SSSSSSSS P20
P21
AV115
YT2_ S02_ P21 nvoYTS02p021 SNVT_count_f (51)
ADF 58 0115 X10 % % Sys 3 Compressor % Full Load Amps SSSSSSSS P21
P22
AV116
YT2_ S02_ P22 nvoYTS02p022 SNVT_count_f (51)
ADF 59 0116 X1 * hrs hrs Sys 3 Total Run Hours SSSSSSSS P22
P23
AV117
YT2_ S02_ P23 nvoYTS02p023 SNVT_count_f (51)
ADF 60 0117 X1 * count count Sys 3 Total # of Starts SSSSSSSS P23
P24
AV118
YT2_ S02_ P24 nvoYTS02p024 SNVT_count_f (51)
ADF 61 0118 X 1 °F °C Sys 3 Highest Motor Temp SSSSSSSS P24
P25
AV119
YT2_ S02_ P25 nvoYTS02p025 SNVT_count_f (51)
ADF 62 0119 X 1 °F °C Sys 4 Highest Motor Temp SSSSSSSS P25
P26
AV120
YT2_ S02_ P26 nvoYTS02p026 SNVT_count_f (51)
ADF 63 0120 X 1 °F °C Sys 4 Oil Temperature SSSSSSSS P26
P27
AV121
YT2_ S02_ P27 nvoYTS02p027 SNVT_count_f (51)
ADF 64 0121 X 1 PSI BAR Sys 4 Oil Pressure SSSSSSSS P27
P28
AV122
YT2_ S02_ P28 nvoYTS02p028 SNVT_count_f (51)
ADF 65 0122 X 1 PSI BAR Sys 4 Suction Pressure SSSSSSSS P28
P29
AV123
YT2_ S02_ P29 nvoYTS02p029 SNVT_count_f (51)
ADF 66 0123 X 1 PSI BAR Sys 4 Discharge Pressure SSSSSSSS P29
P30
AV124
YT2_ S02_ P30 nvoYTS02p030 SNVT_count_f (51)
ADF 67 0124 X 1 % % Sys 4 Compressor % Full Load Amps SSSSSSSS P30
P31
AV125
YT2_ S02_ P31 nvoYTS02p031 SNVT_count_f (51)
ADF 68 0125 X1 * hrs hrs Sys 4 Total Run Hours SSSSSSSS P31
P32
AV126
YT2_ S02_ P32 nvoYTS02p032 SNVT_count_f (51)
ADF 69 0126 X1 * count count Sys 4 Total # of Starts SSSSSSSS P32
P33
AV127
YT2_ S02_ P33 nvoYTS02p033 SNVT_count_f (51)
ADF 70 0127 X1 * hz hz VSD Output Frequency 2 SSSSSSSS P33
P34
AV128
YT2_ S02_ P34 nvoYTS02p034 SNVT_count_f (51)
ADF 71 0128 X 1 % % Sys 3 Flask Tank Feed Valve % Open OOOOOOOO P34
P35
AV129
YT2_ S02_ P35 nvoYTS02p035 SNVT_count_f (51)
ADF 72 0129 X 1 % % Sys 4 Flask Tank Feed Valve % Open OOOOOOOO P35
P36
BV105
YT2_ S02_ P36 nvoYTS02p036 SNVT_switch (95)
BD 34 0165 N/A P36
P37
BV106
YT2_ S02_ P37 nvoYTS02p037 SNVT_switch (95)
BD 35 0166 N/A Chiller Alarm ( 0 = no alarm, 1 = alarm ) P37
P38
BV107
YT2_ S02_ P38 nvoYTS02p038 SNVT_switch (95)
BD 36 0167 N/A P38
P39
BV108
YT2_ S02_ P39 nvoYTS02p039 SNVT_switch (95)
BD 37 0168 N/A P39
P40
BV109
YT2_ S02_ P40 nvoYTS02p040 SNVT_switch (95)
BD 38 0169 N/A 0 / 1 0 / 1 Sys 3 Compressor Run Status SSSSSSSS P40
P41
BV110
YT2_ S02_ P41 nvoYTS02p041 SNVT_switch (95)
BD 39 0170 N/A 0 / 1 0 / 1 Sys 4 Compressor Run Status SSSSSSSS P41
P42
BV111
YT2_ S02_ P42 nvoYTS02p042 SNVT_switch (95)
BD 40 0171 N/A 0 / 1 0 / 1 Sys 3 Economizer Solenoid Valve Status SSSSSSSS P42
see note 3
ENG
PAGE
Ref
BACnet
Object
Typ/Ins
Bacnet Object
Name
LON Profile
Name
LON SNVT Type
N2
Metasys
MODBUS ENG UNITS
ENG
PAGE
Ref
SECTION 2 ELINK
Revision: YCAV_YCIV BAS (Rev K_03g).xlsx Tab: YCAV and YCIV Property of Johnson Controls, York, PA Page: 3

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls York YCIV A Series and is the answer not in the manual?

Johnson Controls York YCIV A Series Specifications

General IconGeneral
BrandJohnson Controls
ModelYork YCIV A Series
CategoryChiller
LanguageEnglish

Related product manuals