SECTION 6 - TECHNICAL DATA
FORM 201.23-NM2
ISSUE DATE: 3/9/2015
6
(SI UNITS)
WATER TEMPERATURE AND FLOWS (CONT'D)
MODEL
NUMBER
YCIV
LEAVING WATER
TEMPERATURE (°C)
COOLER
3
FLOW
(L/S)
AIR ON CONDENSER (°C)
MIN.
1
MAX.
2
MIN. MAX. MIN. MAX
0157(S/P) 4.4 15.6 8.8 42.6 -17.8 51.7
0157(E/V) 4.4 15.6 10.1 47.3 -17.8 51.7
0177(S/P) 4.4 15.6 10.1 47.3 -17.8 51.7
0177(E/V) 4.4 15.6 10.1 47.3 -17.8 51.7
0187(S/P) 4.4 15.6 10.1 47.3 -17.8 51.7
0187(E/V) 4.4 15.6 10.1 47.3 -17.8 51.7
0197(E/V) 4.4 15.6 11.4 47.3 -17.8 51.7
0207(S/P) 4.4 15.6 11.4 50.5 -17.8 51.7
0207(E/V) 4.4 15.6 11.4 47.3 -17.8 51.7
0227(S/P) 4.4 15.6 11.4 50.5 -17.8 51.7
0227(E/V) 4.4 15.6 11.4 47.3 -17.8 51.7
0247(S/P) 4.4 15.6 11.4 50.5 -17.8 51.7
0247(E/V) 4.4 15.6 10.1 47.3 -17.8 51.7
0267(S/P) 4.4 15.6 11.4 50.5 -17.8 51.7
0267(E/V) 4.4 15.6 11.4 50.5 -17.8 51.7
0287(S/P) 4.4 15.6 15.8 75.7 -17.8 51.7
0287(E/V) 4.4 15.6 15.8 75.7 -17.8 51.7
0307(S/P) 4.4 15.6 18.9 75.7 -17.8 51.7
0327(E/V) 4.4 15.6 18.9 75.7 -17.8 51.7
0357(S/P) 4.4 15.6 18.9 75.7 -17.8 51.7
0357(E/V) 4.4 15.6 18.9 75.7 -17.8 51.7
0397(S/P) 4.4 15.6 18.9 75.7 -17.8 51.7
NOTES:
1. For leaving brine temperature below 4.4°C, contact your nearest Johnson Controls ofce for application requirements.
2. For leaving water temperature higher than 15.6°C, contact the nearest Johnson Controls ofce for application guidelines.