Technical data
General data and operating conditions
3
135
EDKVF9333V DE/EN/FR 7.2
Operating conditions
Ambient conditions
Climatic
Storage
IEC/EN 60721−3−1
1K3 (−25 ... +55 °C) < 6 months
1K3 (−25 ... +40 °C) > 6 months
> 2 years: form DC bus
capacitors
Transport IEC/EN 60721−3−2 2K3 (−25 ... +70 °C)
Operation
EVF9321 ... EVF9326
IEC/EN 60721−3−3
3K3 (0 ... +55 °C)
> +40 °C: reduce the rated output current by 2.5 %/°C.
EVF9327 ... EVF9333 3K3 (0 ... +50 °C)
> +40 °C: reduce the rated output current by 2.5 %/°C.
Pollution IEC/EN 61800−5−1 Degree of pollution 2
Site altitude < 4000 m amsl
> 1000 m amsl: reduce the rated output current by
5 %/ 1000 m.
Mechanical
Vibration resistance
(9.81 m/s
2
= 1 g)
Germanischer Lloyd
5 ... 13.2 Hz
Amplitude ±1 mm 13.2 ... 100 Hz:
acceleration resistant up to 0.7 g
IEC/EN 60068−2−6
10 ... 57 Hz
Amplitude 0.075 mm 57 ... 150 Hz:
acceleration resistant up to 1 g
Electrical
AC−mains connection
Max. mains voltage
range
320 V − 0 % ... 528 V + 0 %
Mains frequency 45 Hz − 0 % ... 65 Hz + 0 %
Power system TT, TN Operation permitted without restrictions with earthed
neutral.
Power system IT Operation only permitted with the device variants V024 or
V100.
Operation permitted without restrictions with insulated
neutral.
Observe instructions on specific measures!
Operation on public
supply systems
EN 61000−3−2
Limitation of harmonic currents
Total output at the mains Compliance with the
requirements
1)
< 1 kW With mains choke.
> 1 kW Without additional measures.
1)
The additional measures mentioned have the effect that solely the controllers
meet the requirements of EN 61000−3−2. The machine/system manufacturer is
responsible for the compliance with the requirements for the machine/system!
DC−mains connection
Max. mains voltage
range
450 V − 0 % ... 740 V + 0 %
Operating conditions DC voltage must be symmetrical to PE.
The controller will be destroyed when +U
G
or −U
G
are earthed.
Motor connection
Length of the motor
cable
< 50 m shielded
< 100 m unshielded
At rated mains voltage and a switching frequency of £ 8 kHz
without additional output filter.
For compliance with EMC regulations, the permissible cable
length might change.